@air
2025-05-26

Does the hospital use compressed air?

Technical instructions on the application of compressed air in hospitals

Compressed air plays an indispensable role in the modern hospital operation system, and its application runs through many core aspects such as medical treatment, equipment operation, and environmental control. After systematically reviewing industry specifications and technical practices, relevant application scenarios and technical requirements are explained as follows:

1. Core application areas

  1. life support system
  • Respiratory therapy: Provide powered air source for ventilators and high-frequency oscillating ventilation equipment, and directly participate in respiratory support for critically ill patients
  • Anesthesia delivery: Mixed with oxygen and anesthetic to form therapeutic gas, requiring flow accuracy error ≤±5%
  • Premature infant care: The dedicated breathing bed adopts a constant pressure air supply system, and the pressure fluctuation range needs to be controlled within ±0.02MPa
  1. Operating room dedicated system
  • Device drive: Pneumatic surgical tools (such as orthopedic drills and staplers) require a stable air source of 0.4-0.6MPa
  • Environmental control: The clean operating room adopts a laminar flow purification system, and the compressed air needs to undergo three-level filtration (filtration accuracy reaches 0.01μm)
  • Protective equipment: Lead doors, airtight doors and other protective devices adopt pneumatic control system, response time ≤0.3 seconds
  1. Diagnosis and treatment assistance system
  • Dental treatment: Dental handpiece requires 0.2-0.25MPa dry air source, water content ≤6.3g/m³
  • Disinfection supply: The pulse vacuum sterilizer is driven by compressed air, and the pressure control accuracy reaches ±0.01MPa
  • Inspection and analysis: Precision equipment such as flow cytometers requires clean air sources, with oil content ≤0.01mg/m³
  1. infrastructure operation
  • Central air supply: Continuous air supply to nursing units, intensive care units and other areas through a bus system
  • Standby power supply: The air compressor system is equipped with dual-circuit power supply to ensure automatic switching within 30 seconds in case of sudden power failure
  • Negative pressure suction: Work in conjunction with the vacuum pump group to maintain a negative pressure environment in the diagnosis and treatment area (usually-50Pa to-100Pa)

2. Quality assurance system

  1. Purification process
  • Five-level filtration system: pre-filtration (5μm), precision filtration (1μm), activated carbon adsorption, sterilization filtration (0.01μm), and terminal filtration are configured in sequence
  • Drying treatment: Adopt a combination process of freezing dryer and adsorption dryer, pressure dew point ≤-40℃
  • Monitoring system: real-time detection of 12 indicators such as oil content, microorganisms, and particulate matter, with a data storage period of ≥3 years
  1. special technical requirements
  • Oil-free design: Water-lubricated oil-free air compressors are used in the core area to eliminate the risk of lubricating oil pollution
  • Material standard: The gas transmission pipeline is made of 316L stainless steel, and the inner wall roughness Ra≤0.4μm
  • Disinfection specification: Steam sterilization of pipes every quarter, sterilization temperature 121℃, duration 30 minutes

3. Operation and maintenance management specifications

  1. operation control
  • Pressure management: Set a three-level pressure regulating valve to maintain the supply pressure stable at 0.5 – 0.7MPa
  • Energy efficiency optimization: Using frequency conversion speed regulation technology, no-load energy consumption is reduced by more than 40%
  • Emergency plan: Configure standby units, and the system switching time shall be ≤ 2 minutes in case of single unit failure
  1. inspection and maintenance
  • Daily inspection items: pressure gauge calibration, pipeline leak detection, air tank drainage
  • Weekly inspection items: filter pressure differential inspection, dryer regeneration temperature verification
  • Annual inspection items: tube endoscopy inspection, compressor performance attenuation test

4. Basis for industry norms

  1. Medical gas standard: GB50751 – 2012 Technical Specifications for Medical Gas Engineering
  2. Quality standard: GB/T 14213 – 2013 “Quality Standard for Hospital Compressed Air”
  3. Pipeline specification: GB50316 Code for Design of Metal Pipelines

It is recommended that medical institutions establish a special management system for compressed air systems, allocate full-time operation and maintenance teams, and regularly carry out system performance assessments and risk investigations. When system transformation or new gas equipment is added, load accounting and pipeline verification should be re-carried out to ensure that the quality of gas supply continues to meet medical treatment needs.

Welcome!

Related Articles:
@air
2025-06-06

Can the air compressor be loaded 24 hours a day?

Whether the continuous operation of the air compressor 24 hours a day is reasonable must be comprehensively judged based on equipment performance, operating environment and use needs. The following is explained from four aspects: technical feasibility, potential risks, maintenance costs and optimization suggestions: 1. Technical feasibility…

@air
2025-08-27

How much power does the air compressor need for 0.5-0.6mpa?

The power demand of an air compressor is mainly determined by the supply pressure and the air flow rate. In the pressure range of 0.5- 0.6 MPa (i.e. 5-6bar), the power required is usually proportional to the amount of air used per unit of time (e.g. cubic meters per minute)…

@air
2025-03-31

What is the gas flow rate of the air compressor in the production workshop

The gas flow requirement of air compressors in production workshops is usually 1-20 m³/min, depending on the size of the workshop and equipment requirements. Large or special process scenarios may require higher traffic. When selecting models, current needs, future expansion and environmental factors should be comprehensively evaluated to ensure equipment stability and economy.

@air
2025-07-01

Is it necessary to use frequency conversion for screw air compressors?

Analysis of the necessity of adopting frequency conversion technology for screw air compressors As a mainstream equipment in the industrial field, its energy efficiency performance and operating stability directly affect the company’s production costs and process quality. The introduction of frequency conversion technology provides excellent equipment performance…

@air
2025-03-08

How often do you need to maintain the screw air compressor?

The maintenance cycle of a screw air compressor depends on a variety of factors, including the type of equipment, working environment, frequency of use, and manufacturer’s recommendations. The following is a maintenance cycle guide based on a variety of information: 1. First maintenance of new machines Maintenance cycle: The first maintenance of new machines should […]